STANDARD LOW VOLTAGE BUSHING ASSEMBLIES 1.2 KV CLASS, 30 KV BIL EXTERNALLY CLAMPED TYPE
Technical Specification
Product: Low Voltage Bushing Assembly
Application: Liquid-Filled Transformer
1. Operating Conditions
- Electrical ratings are based on installation and operation in a liquid-filled transformer environment.
- The lower end of the bushing must remain below the oil level during operation.
- 2. Construction and Materials
- Insulating Body: Manufactured from high-quality electrical-grade wet-process porcelain for superior dielectric performance.
- Finish: Standard gray glaze finish (alternative finishes available upon request).
- Mounting: Designed for installation in a 2.69 in (68.3 mm) diameter mounting hole.
- Anti-Rotation Design:
- The bushing is keyed to the two-piece clamp.
- The connector is keyed to the porcelain insulator to prevent rotation during assembly and operation.
3. Gasket Options
- Standard Gasket Material: Nitrile (Buna-N)
- Optional Gasket Material:Cork and rubber composite
- To specify this option, add the suffix “C” to the part number when ordering.
4. Terminal (Spade) Details
- Standard Material: 95% minimum conductivity copper
- Finish: Tin plated for corrosion resistance and enhanced conductivity.
- Optional Materials: Brass, bronze, or other copper alloys available upon request at a discounted price.
5. Design and Compatibility
Designed to ensure mechanical stability and electrical reliability under standard transformer operating conditions.
Compatible with externally clamped transformer mounting configurations.