STANDARD LOW VOLTAGE BUSHING ASSEMBLIES 1.2 KV CLASS, 30 KV BIL EXTERNALLY CLAMPED TYPЕ
Technical Specification
Product: Low Voltage Bushing Assembly
Application: Liquid-Filled Transformer
1. Operating Conditions
- Electrical ratings are based on operation in a liquid-filled transformer, with the lower end of the bushing submerged below the oil level.
- Designed for consistent performance under standard transformer service conditions.
2. Construction and Materials
- Insulating Body: Manufactured from high-quality electrical-grade wet-process porcelain for excellent dielectric strength and mechanical durability.
- Finish: Standard gray glaze, unless otherwise specified.
- Mounting Hole Diameter: 3.94 in (100 mm) minimum.
- Anti-Rotation Design:
- The bushing is keyed to a two-piece clamp.
- The connector is keyed to the porcelain insulator to prevent rotation during installation or operation.
3. Gasket Options
- Standard Gasket Material: Nitrile (Buna-N).
- Optional Gasket Material: Cork and rubber composite.
- To specify this option, add suffix “C” to the part number when ordering.
4. Terminal (Spade) Assembly
- Standard Material: 95% minimum conductivity copper.
- Finish: Tin plated for improved corrosion resistance and electrical contact.
- Optional Materials: Lower-conductivity copper alloys (e.g., brass, bronze) available upon request at discounted pricing.
5. Design Features
Engineered to ensure long-term performance under oil-immersed conditions.
Suitable for externally clamped transformer installations.
Provides mechanical stability, precise alignment, and electrical reliability.