STANDARD LOW VOLTAGE BUSHING ASSEMBLIES 1.2 KV CLASS, 30 KV BIL EXTERNALLY CLAMPED TYPE
Technical Specification
Product: Low Voltage Bushing Assembly
Application: Liquid-Filled Transformer
1. Operating Conditions
- Electrical ratings are based on use in liquid-filled transformers, with the lower end of the bushing submerged below the oil level during operation.
- Designed for stable electrical and mechanical performance in standard transformer service environments.
2. Construction and Materials
- Insulating Body: Manufactured from premium electrical-grade wet-process porcelain for excellent dielectric strength and long-term durability.
- Finish: Standard gray glaze, unless otherwise specified.
- Mounting Hole Diameter: 3.94 in (100 mm) minimum.
- Anti-Rotation Design:
- The bushing is keyed to a two-piece clamp.
- The connector is keyed to the porcelain insulator, preventing rotation during installation and operation.
3. Gaskets
- Standard Gasket Material: Nitrile (Buna-N).
- Optional Gasket Material: Cork and rubber composite.
- To specify this option, add suffix “C” to the part number when ordering.
4. Terminal (Spade) Assembly
- Standard Material: 95% minimum conductivity copper.
- Finish: Tin plated to ensure optimal corrosion resistance and electrical performance.
- Optional Materials: Lower-conductive copper alloys (such as brass or bronze) available upon request at discounted pricing.
5. Design Features
- Designed for externally clamped transformer mounting configurations.
- Provides mechanical stability, precise alignment, and resistance to rotation during operation.
- Ensures long-term electrical reliability in oil-immersed applications.